HMP260 SERIES
Operating Manual HMP260-U017en-1.5
16 1997-11-25
CH2 CURRENT OUTPUT
CH1 0 ... 1 VOLTAGE OUTPUT
CH1
CH2
CH2
CH1
X15
CURRENT OUTPUTS
0 ... 20 / 4 ... 20 mA
VOLTAGE OUTPUTS
0 ... 5 V / 0 ... 10 V
VOLTAGE OUTPUTS
0 ... 1 V
CH1
CH2
CH2
CH1
CH1
CH2
CH2
CH1
CH1
CH2
CH2
CH1
OPENED COVER OF THE HMP260
Fig. 4.2 Selecting the analogue outputs with jumpers
The software has to be informed which outputs are in use. This is done either
through the serial interface or the menus on local display when one is in use.
The serial command is AMODE and the display/keypad command "Mode
Analog outputs Mode" (see Chapter 5 Commands). If the outputs need to
be scaled, see serial command ASCL and the display command "Mode
Analog outputs Scale".
All the jumpers are used only with the 0...1 V outputs. When other outputs are
in use, the spare jumpers are kept in connector X55.