Chapter 4 _________________________________________________________________ Operation
VAISALA ________________________________________________________________________ 29
CHAPTER 4
OPERATION
This chapter contains information that is needed to operate the HMP60
and HMP110 series probes.
Getting Started
NOTE
Before you connect a
n HMP60 or HMP110 series probe to a device, it is
recommended to power off the device.
When the probe is connected to a power supply, there is a delay as the
probe starts up and the analog output stabilizes. The delay depends on the
output type, and on the operating voltage that is supplied to the probe:
- Probes with analog output:
- 4 s at operating voltage 13.5 ... 16.5 VDC
- 2 s at other valid operating voltages
- Probes with digital output: 1 s
Serial Line Communication
NOTE
In analog probes,
serial line communication is intended for service use
only.
HMP60 and HMP110 series probes support two-wire RS-485
communication. The RS-485 interface is non-isolated and offers a
maximum communications rate of 57600 bits/s.
There is no internal termination for the RS-485 on the probe. Use of
termination resistors is not recommended. If the resistors are used, the
possible increase in current consumption should be taken into account.