Vaisala HUMICAP HMW90 SERIES Specifikace Strana 68

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 74
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 67
HUMIDITY
562
HUMIDITY
9
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
Supply Voltage 24 VAC ±10% 3 VA, 50-60 Hz; 24
VDC, 125 mA
Accuracy ±3% RH (20%-80%)
Signal Output
Analog 0/2-10 VDC or 0/4-20 mA @250
Digital 24 VAC/VDC @ 2 A
Signal Input
13 0/2-10 VDC or 0/4-20 mA @ 240
23 0/2-10 VDC or 0/4-20 mA @ 240 &
10k Type II thermistor (24)
Measurement Range 0 to 100 % RH
Operating Humidity 0% to 95% non-condensing
Operating Temperature 32° to 122°F (-25° to 50°C)
Enclosure Rating ABS Plastic
Sensing Technology Capacitive sensor
Wiring Terminations Terminal block (12 to 24 AWG)
Dimensions 4.4" H x 2.9" W x 1.8" D
(11.2 x 7.3 x 4.7 cm)
Approvals CE
Weight
13 0.58 lb (0.26 Kg)
23 0.6 LB (0.27 kG)
Warranty 2 years
3% WALL AND DUCT PROPORTIONAL CONTROLLER
TCI SERIES
DESCRIPTION
The Vector Model TCI Wall and Duct Proportional
Controller is designed for proportional control of
humidification and dehumidification equipment in HVAC and
energy management systems. The "23" models comes with
a time clock for advanced programming with 48 hour backup
and the "13" models do not. The "H" models have internal
relative humidity sensors and the others without "H" in model
number must use a remote relative humidity sensor (ordered
separately) for RH measurement.
FEATURES
Humidification and dehumidification control
External temperature input for set point setback
Programmable user interface
Optional time clock
2 analog outputs and one digital output
Easy to read display
SPECIFICATIONS
TCI
Zobrazit stránku 67