GMW115 Carbon Dioxide Transmitter for
Demand-controlled Ventilation
The Vaisala CARBOCAP
®
Carbon Dioxide Transmitter GMW115 is a wall-mounted
CO
2
transmitter for demand-controlled ventilation.
Most of us spend 90 % of our time
indoors. Consequently, good indoor
air quality is important to our
wellbeing. All human beings produce
carbon dioxide gas by respiration,
thus the carbon dioxide level can
be used as an indicator for indoor
human presence. A high CO
2
level is a
sign of poor ventilation and often an
indication of other unpleasant odors
in the air. In many buildings the
ventilation need varies throughout
the day. Demand controlled
ventilation is an economical way to
ensure good air quality.
The Vaisala CARBOCAP
®
CO
2
sensors have been proven to be
accurate and durable. They have
an excellent long-term stability,
which decreases maintenance. The
superior performance of Vaisala
CARBOCAP
®
sensors results largely
Features/Benefi ts
Compact, wall-mounted
transmitter for demand-
controlled ventilation
Incorporates Vaisala
CARBOCAP®, the silicon based
NDIR sensor with unique
internal referencing
Advanced, single-beam, dual
wavelength measurement with
no moving parts
Excellent long-term stability
Ideal for ventilation control in
all types of occupied spaces
from the stable reference provided by
the electrically tunable Fabry-Perot
Interferometer (FPI).
The tunable FPI  lter measures CO
2
absorption, and simultaneously a
reference wavelength. This internal
reference measurement compensates
effectively for any changes in the
optical path, such as light source
intensity changes and contamination.
In the HVAC market, this type of
reference measurement is a unique
feature to Vaisala CARBOCAP
®
products, distinguishing them
from competitors’ comparative
products that do not have a reference
measurement at all, or have an
indirect reference measurement,
which is based on an assumed back-
ground CO
2
levels. In buildings with
around-the-clock occupancy (e.g.
hospitals, work-places, residential
buildings, retirement homes), the
assumed background CO
2
level
reference is simply not applicable.
The true internal reference
measurement of Vaisala CARBOCAP
®
CO
2
transmitters provides years of
stable CO
2
measurements.
The GMW115 Transmitter is designed
especially for DCV (Demand Controlled
Ventilation) applications with two
optional CO
2
measurement ranges of
02000 ppm and 0…5000 ppm.
Zobrazit stránku 107